High Sensitive Smoke Detection System (HSSD)- Aspirating Smoke Dedectors (ASD); high sensitive smoke detectors are used in sensitive sensing applications used in systems that require early warning and very early warning. The system constantly measures and controls the air in the environment. It monitors the size of particles in the air through multiple sampling holes at the same location.
An air sampling detector can have one, two and four channels, depending on the brand used. The length of each air sampling channel is maximum 100 meters in a single channel and 160 meters in a channel with a branch pipe. The diameter and number of holes in the air sampling pipe are determined by a hydraulic calculation program depending on the length of the air sampling pipe. There is no more than 10m distance between air sampling holes.
It has blue leds and infrared ray technology, communication feature and integration with different systems. It can operate independently or can be monitored with a control panel and fire alarm and detection panel. It has its own audible alarm system. Wide area detection up to 2000 m2 can be done with a sensitive air sampling detector. Maintenance costs are low.
Operating temperature 0°C (32°F) / 38°C (100° F), sampling air temperature -20°C (-4°F) / 60°C (140°F), Ambient humidity 10 – 95%, IP 30 protection class and air movement 0-1,219 m / min. (0-4,000 ft./min.).